B-65282EN/05 APPENDIX A.FITTING A LIGHTNING SURGE PROTECTION DEVICE
- 297 -
A.3 CAUTIONS
(1) To increase the efficiency of lightning surge absorption, the
wires indicated by bold lines should be as short as possible.
Wire cross-sectional area : 2 mm
2
or more
Wire length :
The total length of the cables used for line-to-line lightning
surge protector (a) and that used for line-to-ground
lightning surge protector (b) must not exceed 2 m.
(2) When performing a dielectric strength test by applying an
overvoltage to the power line, line-to-ground lightning surge
protector must be removed to enable the applied voltage to be
maintained.
(3) The circuit breaker 2 (5A) or circuit breaker 3 (5A) works for
line protection when the lightning surge absorber is short-
circuited because of a surge higher than its rating being applied.
(4) Because current does not flow through lightning surge protector
in a normal state, the circuit breaker 2 (5A) or circuit breaker 3
(5A) can be used together with the surge absorbers as well as
with other equipment.