2.SPECIFICATIONS B-65282EN/05
- 14 -
(3) It is recommended that a capacitor unit for power-factor
improvement not be installed. This is because the capacitor unit
for power-factor improvement may adversely affect power
regeneration.
(4) The rated output of the motor is guaranteed for the rated input
voltage. If the input voltage changes, the rated output may not
appear even when the input voltage change is within the
allowable range.
(5) When the power supply is used in an area where the input
voltage is not within the range of 200 to 240 VAC, a power
transformer is required. When a power transformer is to be
provided by the user, the power must satisfy the specifications
listed below.
(6-1) PSM
Table 2.1(a) Transformer Specifications
PSM-5.5i PSM-11i PSM-15i PSM-26i PSM-30i PSM-37i
PSM-55i
(45kW output)
PSM-55i
(55kW output)
Rated capacity (kVA)
9 1722374453 64 79
Secondary current (A)
26 48 62 105 130 153 185 230
Secondary output
voltage
200 to 240 V
Secondary voltage
regulation
5%
Secondary voltage
deviation
±3%
(6-2) PSMR
Table 2.1(b) Transformer Specifications
PSMR-3i
(2kW output)
PSMR-3i
(3kW output)
PSMR-5.5i
(5.5kW output)
PSMR-5.5i
(7.5kW output)
Rated capacity (kVA)
3.5 5 9 13
Secondary current (A)
10 14 26 38
Secondary output
voltage
200 to 240 V
Secondary voltage
regulation
5%
Secondary voltage
deviation
±3%
(7) Ground
The main circuit and 200V control power supply must be
grounded through the neutral point or one phase of the three-
phase power supply.
(8) Noise filter
To satisfy the EMC regulation enforced in the EU countries, a
noise filter must be installed in the PSM input section.