5. PERIODIC MAINTENANCE
B-65165E/02 START-UP PROCEDURE OF SERVO AMPLIFIER
- 87 -
5.1.2 Using a Battery Case (A06B-6050-K060) (Method 2)
Details of connection of the battery unit to the SVM
Screw terminal: M3
Crimp terminal: 1.25-4
+6 V
Battery unit
0 V
SVM
CX5X, CX5Y (2)
CX5X, CX5Y (1)
0.3 mm
2
×
2
Housing : 1L-L2S-S3L-B(N)
Contact : 1L-C2-1-00001
Manufacturer: Japan Aviation Electronics
Industry, Ltd.
Note) A special crimping tool is required to attach the contacts to a
cable. Contact the following:
Japan Aviation Electronics Industry, Ltd.
WARNING
1 Install the battery with correct polarity. If the battery
is installed with incorrect polarity, it may overheat,
blow out, or catch fire.
2 When installing the battery with its connector
attached to connector CX5X or CX5Y, attach the
factory-installed protection socket to the unused
connector. When the +6-V and 0-V pins of CX5X or
CX5Y are short-circuited, the battery may overheat,
blow out, or catch fire.
CAUTION
1 You may attach the battery connector to either CX5X
or CX5Y.
2 To an unused connector, attach the supplied
protection socket.