4. CONFIRMATION OF
B-65165E/02 START-UP PROCEDURE THE OPERATION
- 49 -
4.3 SPINDLE AMPLIFIER MODULE
Check each item according to the procedure described below.
9. Check the operation in normal operation mode (S command).
8. Make sure that the magnetic contactor for PSM input is turned on.
See Section 4.1.
7. Release the system from the emergency stop state.
6. Check the waveform on the detector. See Subsection 4.3.4.
5. Set and check spindle-related parameters. (The parameter manual
is required.)
No Yes
4. Prepare and check a PMC ladder. (The descriptions manual is
required.)
3. Has the system been used with this connection status?
OK Alarm issued.
See Section 3.4 of Part II.
2. Check the STATUS display. See Subsection 4.3.1.
1. Supply control power (200 VAC) to the PSM, and turn on the power
to the CNC.