6. CONNECTION OF I/O UNITS TO
MACHINE INTERFACE
B–63173EN/03
130
Ambient temperature During operation 0° to 55°C
During storage and transportation –20°C to 60°C
Relative humidity 30 to 95% (no condensation)
Vibration During operation: 0.5 G or less
Environment Inter of units: Each unit should be placed in a cabinet
to keep it from pollutants (such as dust, coolant,
organic solvents, acid, corrosive gas, and salt).
Other requirements
(1) Install the I/O module in a fully enclosed cabinet.
(2) To ensure adequate ventilation between I/O
modules, install them as shown in the figure
below. Allow a minimum of 100 mm above and
below each module for wiring and ventilation. Do
not place heat–generating apparatus under the
I/O modules.
(3) Ensure that the flat cables do not cover the vents
of the basic unit. For details, see 6.7.8.
Extension unit 1
Extension unit 2
Extension unit 3
Top
I/O Link connection
MPG connection
Bottom
Basic unit
Item Specification Remarks
Connector panel I/O
module basic
A03B–0815–C001 DI/DO: 24/16
Connector panel I/O
module extension A
A03B–0815–C002
DI/DO: 24/16 with MPG
interface
Connector panel I/O
module extension B
A03B–0815–C003 DI/DO: 24/16
Connector panel I/O
module expansion C
A03B–0815–C004
DO: 16
2A
Connector panel I/O
module expansion D
A03B–0815–C005 Analog input
Fuse (replacement part) A03B–0815–K002 1 A
Flat cable for unit
connection
A03B–0815–K100
Cable length: 20 mm
(when units are spaced 32 mm
apart)
6.7.11
Specifications
Installation
specifications
Ordering specifications