3.TROUBLESHOOTING AND ACTION TROUBLESHOOTING FOR βi SVPM B-65325EN/01
- 130 -
3.1.4 STATUS2 Alarm Code -
STATUS1 Alarm Code 51
(1) Meaning
In the main circuit, the DC voltage (DC link) has dropped.
(2) Cause and troubleshooting
(a) A small power dip has occurred.
→ Check the power supply.
(b) Low input power supply voltage
→ Check the power supply specification.
(c) The main circuit power supply may have been switched off
with an emergency stop state released.
→ Check the sequence.
3.1.5 STATUS2 Alarm Code -
STATUS1 Alarm Code 33
(1) Meaning
The main circuit capacitor was not recharged within the specified
time.
(2) Cause and troubleshooting
(a) Too many SVM and/or SVPM units are connected.
→ Check the specification of the SVPM.
(b) The DC link is short-circuited.
→ Check the connection.
(c) The recharge current limiting resistor is defective.
→ Replace the distributing board.
3.1.6 STATUS2 Alarm Code -
STATUS1 Alarm Code b1
(1) Meaning
The control power supply voltage decrease.
(2) Cause and troubleshooting
(a) Input voltage decrease
→ Check the power supply.