B-65325EN/01 TROUBLESHOOTING FOR βi SVPM 3.TROUBLESHOOTING AND ACTION
- 139 -
3.3.3 Overload Alarm (Soft Thermal, OVC)
(Alarm identification method)
#7 #6 #5 #4 #3 #2 #1 #0
<1> Alarm 1
OVL LVA OVC HCA HVA DCA FBA OFA
(Action)
(1) Make sure that the motor is not vibrating.
Þ If a motor vibrates, the current flowing in it becomes more
than necessary, resulting in an alarm.
(2) Make sure that the power lead to the motor is connected correctly.
Þ If the connection is incorrect, an abnormal current flows in
the motor, resulting in an alarm.
(3) Make sure that the following parameters are set correctly.
Þ An overload alarm is issued based on the result of calculation
of these parameters. Be sure to set them to the standard
values. For details of the standard values, refer to the FANUC
AC SERVO MOTOR αis/αi/βis series Parameter Manual
(B-65270EN).
(4) Check the operation conditions. The machine load may be too
heavy for the motor specification.
No.2062 (FS0i)
Overload protection coefficient (OVC1)
No. 2063 (FS0i)
Overload protection coefficient (OVC2)
No. 2065 (FS0i)
Overload protection coefficient (OVCLMT)
No. 2162 (FS0i)
Overload protection coefficient (OVC21)
No. 2163 (FS0i)
Overload protection coefficient (OVC22)
No. 2164 (FS0i)
Overload protection coefficient (OVCLMT2)