3.PERIPHERAL EQUIPMENT CONTROL HANDLING B-65395EN/01
- 122 -
NOTE
1 This parameter is valid when parameter No. 020 is
set to 1.
2 This parameter is also valid when bit 5 of parameter
No. 007 is 1 (a turret/magazine number is always
output to response data).
No
020 Response data specification (PHOUT)
[Size] 1 byte
[Standard setting value] 3
PHOUT Specifies whether or what to output as response data (Xx+3 to Xx+6),
as follows:
0 : Nothing is output.
1 : An ATC and point No. are output if an ATC cycle and point
positioning are involved.
2 : Machine coordinates are output in real time.
3 : Workpiece coordinates are output in real time.
4 : The motor current value is output. The motor current value is
6554, which is the maximum current value for the amplifier.
5 : Measurement data (workpiece coordinates) obtained when a skip
signal is input is output.
6 : An actual feedrate is output in real time.
[Unit of data] 10
N
User-specified unit/MIN (N:Parameter No. 021)
7 : An actual speed is output in real time.
[Unit of data] min
-1
8 : A torque command is output in real time. The maximum value of
a torque command is 6554.
The least significant bit is a signal indicating whether the torque
limit is reached.
Least significant bit =
0: The torque limit is not reached.
1: The torque limit is reached.
NOTE
1 If the motor current value is output as response
data, set LDM (bit 6 of parameter No. 005) to "1"
and set "4" for parameter No. 020.
2 This parameter is also valid when bit 5 of parameter
No. 007 is 1 (a turret/magazine number is always
output to response data).
3 The value of an actual speed is output with a sign.
While the motor is being stopped, the motor current
may drift, causing the sign to be unstable.