B.PARAMETER LIST APPENDIX B-65395EN/01
- 266 -
LIMITATIONS
When this parameter is used, the limits below are
imposed on the settings of the amount of movement
per rotation axis revolution (parameter No. 141),
command multiplier (CMR) (parameter No. 032),
and denominator for the number of pulses per motor
revolution (SDMR2) (parameter No. 106). If any of
the limits is exceeded, this parameter cannot be
used.
Amount of movement per rotation axis revolution
(parameter No. 141) × K
× Denominator for the number of pulses per motor
revolution (parameter No. 106) ≤ 247 - 1
where
K =
• When K ≥ 1, CMR = 2 × K (1 ≤ K ≤ 48).
(When expanded CMR (parameter No. 138) is
used, however, 1 ≤ K ≤ 200.)
• When K < 1, CMR = 1/K + 100 (1/2 ≤ K ≤ 1/27).
If K ≥ 1, the above conditional expression applies.
If K < 1, the conditional expression does not
require the K term, and is set as follows.
Amount of movement per rotation axis revolution
(parameter No. 141)
× Denominator for the number of pulses per
motor revolution (parameter No.106) ≤ 247 - 1
APCX Indicates whether a detector for an absolute pulse coder is available.
0 : Unavailable
1 : Available
No #7 #6 #5 #4 #3 #2 #1 #0
012 DGPR
[Size] 1 byte (bit type)
[Standard value] 0
DGPR Specifies whether to set motor-specific servo parameters when the
power is switched on.
0 : Set.
1 : Do not set.
After a motor type (parameter No. 30) is specified, resetting this bit to 0
automatically sets up the standard values for the motor when the power
is turned on. At the same time, the bit is set to 1 again.
User-specified unit
Detection unit