7.QUICK STOP FUNCTION HANDLING B-65395EN/01
- 186 -
7.4 PARAMETER
No #7 #6 #5 #4 #3 #2 #1 #0
018 TIM1 TIM0 VCMD0
[Size] 1 byte/bit type
VCMD0(#2) Quick stop function is:
0 : Disabled.
1 : Enabled.
TIM1,0(#4,#3) Setting of the MCC off timer
The delay time from the time an emergency stop signal is input until
MCC is turned off can be selected with a combination of TIM1 and
TIM0. If VCMD0 is 0, the setting is invalid.
Usually set it to 60 ms. If a sufficult effect cannot be obtained, set it to
100 ms.
Delay time TIM1 TIM0
0ms 0 0
60ms 1 0
100ms 1 1
NOTE
1 It is not possible to set a delay time of 100 ms or
greater by mounting an additional external timer.
2 Do not turn an emergency stop OFF/ON
instantaneously.
3 The timer on the amplifier operates in conjunction
with connector CX30 or with *ESP on CXA19B. It
does not operate only with an emergency stop
signal on the FANUC I/O Link between the host and
a servo amplifier module.