B--65245EN/02
2. SIGNAL DESCRIPTIONSHANDLING
49
*OV8 *OV4 *OV2 *OV1 Override value (%)
1 1 1 1 0
1 1 1 0 10
1 1 0 1 20
1 1 0 0 30
1 0 1 1 40
1 0 1 0 50
1 0 0 1 60
1 0 0 0 70
0 1 1 1 80
0 1 1 0 90
0 1 0 1 100
0 1 0 0 110
0 0 1 1 120
0 0 1 0 130
0 0 0 1 140
0 0 0 0 150
Actual jog feed and automatic cutting feedrates are obtained by
multiplying the respective specified values by the override values.
(2 ) Manual rapid traverse selection signal RT
[Classification]
Output signal <Yy+7#7> (peripheral equipment control interface)
<Yy+2#7> (direct command interface)
[Function]
The host selects rapid traverse for jog feed.
[Operation]
The RT signal is valid when jog feed mode (JOG) is selected. When
the signal is 1, jog feed is performed at a rapid traverse rate. Under
this condition, setting a feed axis and direction selection signal (+X
or --X) to 1 starts rapid traverse in the specified direction. If jog feed
is selected, a feed axis and direction selection signal (+X or --X) is 1,
and an override signal is valid, setting t he RT signal to 1 starts rapid
traverse. Resetting the RT signal to 0 resumes normal feed.
(3) Rapid traverse override signals ROV1 and ROV2
[Classification]
Output signal <Yy+7#4 and #5> (peripheral equipment control
interface)
<Yy+2#4 and #5> (direct command interface)
[Function]
The host specifies override for rapid traverse.
[Operation]
The following table lists the override amounts.
ROV2 ROV1 Override amount
0 0 100%
0 1 50%
1 0 25%
1 1 F0
NOTE
F0 is a value specified in parameter No. 061.