H. DESCRIPTION OF PARAMETERS
B–63443EN/02
APPENDIX
306
1829 Positioning deviation limit for each axis in the stopped state
Data type: Word axis
Unit of data: Detection unit
Valid data range: 0 to 32767
Set the positioning deviation limit in the stopped state for each axis.
If, in the stopped state, the positioning deviation exceeds the
positioning deviation limit set for movement, a servo alarm is
generated, and operation is stopped immediately (as in emergency
stop).
1850 Grid shift for each axis
Data type: 2-word axis
Unit of data: Detection unit
Valid data range: 0 to"99999999
A grid shift is set for each axis.
To shift the reference position, the grid can be shifted by the amount
set in this parameter. Up to half of the maximum value counted by
the reference counter can be specified as the grid shift.
NOTE
1 When this parameter has been set, the power must be
turned off before operation is continued.
2 After this parameter is set, return to the reference position is
required again.
1851 Backlash compensating value for each axis
Data type: Word axis
Unit of data: Detection unit
Valid data range:*9999 to +9999
Set the backlash compensating value for each axis.
When the unit moves in the direction opposite to the reference
position return direction after the power is turned on, the first
backlash compensation is performed.