9. DIGITAL SERVO
B–63525EN/02
682
2) Axis setting screen
AXIS SETTING O1000 N00001
AXIS NAME AMP M1 M2 1–DSF Cs TNDM
1XA1–L 0 00 01
2YA1–M 1 0 1 0 0
3ZA2–L 0 0 0 1 0
4AA3–L 0 0 0 0 2
5BA3–M 0 0 0 0 0
6CA4–L 0 0 0 0 0
>_
MDI **** *** *** 13:11:56
[SETTING][ ][ READ ][ ][ INPUT ]
On the axis setting screen, the following items can be specified:
D M1 (connector number for pulse module 1)
For an axis that uses pulse module 1, enter a connector number using
a number in the range of between 1 and the maximum number of axes
for pulse module 1. When pulse module 1 need not be used, enter 0.
If a number that falls outside the valid range is entered, the warning
message “INVALID FORMAT” is displayed.
D M2 (connector number for pulse module 2)
For an axis that uses pulse module 2, enter a connector number using
a number in the range of between 1 and the maximum number of axes
for pulse module 2. When pulse module 2 need not be used, enter 0.
If a number that falls outside the valid range is entered, the warning
message “INVALID FORMAT” is displayed.
D 1–DSF
Enter 1 for the following axes, each of which exclusively uses a DSP,
which is usually shared by two–axes. If a number other than 0 or 1 is
entered, the warning message “INVALID FORMAT” is displayed.
⋅ Learning control axis
⋅ High–speed current loop axis
⋅ High–speed interface axis
D Cs (Cs contour controlled axis)
Enter 1 for the Cs contour controlled axis. If a number other than 0
or 1 is entered, the warning message “INVALID FORMAT” is
displayed.
D TNDM
Enter odd and even numbers for the master and slave axes for tandem
control. These numbers must be consecutive and in the range of
between 1 and 8. If a number that falls outside the valid range is
entered, the warning message “INVALID FORMAT” is displayed.