[Classification] Output signal
[Function] This signal indicates that the actual spindle speed is not within a tolerance
to the specified speed.
[Output condition] The signal becomes logical “1” when:
⋅ The actual spindle speed goes out of tolerance to the specified speed.
The signal becomes logical “0” when:
⋅ No alarm condition has been detected for spindle speed fluctuation.
⋅ An alarm condition is cleared by resetting the NC when the signal is
logical “1”.
#7 #6 #5 #4 #3 #2 #1 #0
F035 SPAL
#7 #6 #5 #4 #3 #2 #1 #0
3708 SVD
[Data type] Bit
SVD When the SIND signal is on, the detection of spindle speed fluctuation is:
0 : Disabled
1 : Enabled
#7 #6 #5 #4 #3 #2 #1 #0
4900 FLR
[Data type] Bit
FLR When the spindle speed fluctuation detection function is used, the rates of
allowance (q) and fluctuation (r) those are set in parameter No. 4911 and
No. 4912, respectively are set in steps of:
0 : 1%
1 : 0.1%
Signal
Spindle fluctuation
detection alarm signal
SPAL <F035#0>