B–63523EN–1/03
2. PREPARATIONS FOR OPERATION
361
#7
BFA1300
#6
LZR
#5 #4 #3 #2
LMS
#1
NAL
#0
[Data type] Bit
NAL Specifies whether to issue an alarm related to stored stroke check 1, as
follows:
0 : To issue an alarm.
1 : Not to issue an alarm; the stroke limit reached signal F124 or F126 is
output (for a manual operation).
LMS The EXLM signal for switching stored stroke check 1
0: Disabled
1: Enabled
LZR Checking of stored stroke check 1 during interval between power–on and
setting the manual position reference return
0: The stroke check 1 is checked.
1: The stroke check 1 is not checked
NOTE
When the absolute–position detector is being used, and the
reference position is already set at power–on, the stored
stroke check is checked immediately after the power is
turned on, regardless of the setting of this bit.
BFA When a command is issued where the resulting motion would exceed the
value of stored stroke check 1 or 3
0: An alarm is generated after the stroke check 1, 3 is exceeded.
1: An alarm is generated before the stroke check 1, 3 is exceeded.
#7
1301
#6 #5
OTF
#4
OF1
#3 #2 #1 #0
DLM
[Data type] Bit
DLM Axis direction dependent stored stroke limit switch signals +EXL1 to
+EXL8 and –EXL1 to –EXL8 <G104 and G105> are
0: Disabled.
1: Enabled
OF1 If the tool is moved into the range allowed on the axis after an alarm is
generated by stored stroke check 1,
0: The alarm is not canceled before a reset is made.
1: The OT alarm is immediately canceled.
Parameter