1910 Multiplication of the maximum permissible synchronous error immediately
after power-on
NOTE
After this parameter has been set, the power must be
off turned off then back on for the setting to become
effective.
[Input type] Parameter input
[Data type] Integer
[Valid data range] 1 - 100
Synchronous error alarm 2 is checked with the value equal to the
maximum permissible error (parameter No. 1913) multiplied by the
value of this parameter until synchronization is established
immediately after power-on.
If the value exceeds 32767, it is clamped to 32767.
1912 Dead zone for the synchronous error on each axis
[Input type] Parameter input
[Data type] Integer axis
[Unit of data] detection unit
[Valid data range] 1 - 32767
When the synchronous error does not exceed the setting, it is not
compensated for.
Specify this parameter only for a slave axis.
1913 Maximum permissible synchronous error for synchronous error alarm 2
NOTE
After this parameter has been set, the power must be
off turned off then back on for the setting to become
effective.
[Input type] Parameter input
[Data type] Integer axis
[Unit of data] detection unit
[Valid data range] 1 - 32767
Specify the maximum permissible synchronous error for synchronous
error alarm 2.
Specify this parameter only for a slave axis.