4.DESCRIPTION OF PARAMETERS B-63790EN/01
- 156 -
2015 Time that invalid mode selected status is ignored
[Input type] Parameter input
[Data type] Integer
[Unit of data] msec
[Valid data range] 0 - 2000
If an invalid combination of mode signals is input, the previously
selected mode is maintained for the specified time that the invalid
mode selected status is ignored. After that, the mode unselected status
is specified.
Normally, specify the time needed to ignore mode signal chatter.
2016 Manual feedrate override clamp value
[Input type] Parameter input
[Data type] Integer
[Unit of data] 0.01%
[Valid data range] 0 - 65534
This parameter specifies the value used to clamp the manual feedrate
override when an override value larger than the manual feedrate
override clamp value is input. This parameter is valid only when the
basic machine interface (BMI) is used.
2020 Positive (+) direction command button on the software operator's panel
[Input type] Parameter input
[Data type] Integer axis
[Valid data range] 0 - 9
Specify the number of the numeric (arrow) key on the MDI panel
which instructs manual feed in the positive (+) direction on the
software operator's panel for each axis. The setting of 5 cannot be
used because the numeric key 5 is fixed to the manual rapid traverse
switch.
This parameter can be used for the first to sixth axes. It is ignored for
the seventh and subsequent axes.
Specifying 0 means that the MDI panel does not have any numeric
key that instructs the positive (+) direction.
Example
If 6 is set for the 1st axis:
Numeric key 6 instructs the + direction of the 1st axis.
If 9 is set for the 2nd axis:
Numeric key 9 instructs the + direction of the 2nd axis.
If 8 is set for the 3rd axis:
Numeric key 8 instructs the + direction of the 3rd axis.