B-63790EN/01 4.DESCRIPTION OF PARAMETERS
- 63 -
1080 Address conversion table value (ATR) for slave 1
1081 Address conversion table value (ATR) for slave 2
1082 Address conversion table value (ATR) for slave 3
1083 Address conversion table value (ATR) for slave 4
1084 Address conversion table value (ATR) for slave 5
1085 Address conversion table value (ATR) for slave 6
1086 Address conversion table value (ATR) for slave 7
1087 Address conversion table value (ATR) for slave 8
1088 Address conversion table value (ATR) for slave 9
1089 Address conversion table value (ATR) for slave 10
NOTE
After this parameter has been set, the power must be
off turned off then back on for the setting to become
effective.
[Input type] Parameter input
[Data type] Integer
[Valid data range] From 0 through 7 or 16 or 40 or 48
This parameter is automatically specified when the FSSB setting
mode is the automatic setting mode (bit 0 of parameter No. 1090 is set
to 0) . When the mode is the manual setting mode (bit 0 of parameter
No. 1090 is set to 1) , be sure to directly enter the desired value.
Set the address conversion table values for slaves 1 to 10.
The term slave is a generic name for a servo amplifier or pulse
module connected to the CNC via an FSSB optical cable. Slaves are
assigned numbers 1 to 10, the slave nearest the CNC being assigned 1.
A 2-axis amplifier consists of two slaves, and a 3-axis amplifier
consists of three slaves. Set the appropriate value for this parameter
depending on whether a slave exists and, if it exists, whether the slave
is an amplifier or pulse module, as follows:
- If the slave is an amplifier:
Set the value equal to the setting of parameter No. 1023 for the
axis to which the amplifier is to be assigned, minus 1.
- If the slave is a pulse module:
Set 16 for the first pulse module (connected nearer the CNC) and
48 for the second (connected farther from the CNC) .
- If a slave does not exist:
Set 40.