B-65232EN/03 CONNECTION4.DETAILS OF CABLE CONNECTIONS
- 245 -
4.5 K5 CABLE CONNECTION
4.5.1 FOR FSSB Interface or PWM Interface
β series amplifier
JX5 (20)
JX5 (17)
+24V
*ESP
Emergency stop contact
Wire to be used : 0.18 mm
2
or more
Housing : PCR-V20LA
Connector : PCR-E20FA
Manufacturer : Honda Tsushin Kogyo
NOTE
When the contact is on (closed), the servo motor is
ready for operation. When the contact is off (open),
the external magnetic contactor (MCC) is off,
disabling the servo motor.
If the contact is turned off (open) during motor
rotation, the servo motor stops with a dynamic
brake.
Contact input signals must satisfy the following
requirements:
The external contact is rated at 30VDC, 100mA or
higher.
The significant levels for no-contact inputs (if used)
are:
Low level (logic 0) = not higher than 2V
High level (logic 1) = not lower than 20V