B–63173EN–1/01
1. AXIS CONTROL
51
(2)Axis setting screen
AXIS SETTING O1000 N00001
AXIS NAME AMP M1 M2 1–DSP CS TNDM
1 X A1–L 0 0001
2 Y A1–M 1 0 1 0 0
3 Z A2–L 0 0 0 1 0
4 A A3–L 0 0 0 0 2
5 B A3–M 0 0 0 0 0
6 C A4–L 0 0 0 0 0
>_
MDI **** *** *** 13:11:56
[ SETING ][ ][ CANCEL ][ ][ INPUT ]
On the axis setting screen, the following items can be specified:
D M1 connector number for pulse module 1. . .
For an axis that uses pulse module 1, enter a connector number
using a number in the range of between 1 and the maximum number
of axes for pulse module 1. When pulse module 1 need not be used,
enter 0. If a number that falls outside the valid range is entered, the
message FORMAT ERROR is displayed.
D M2 connector number for pulse module 2. . .
For an axis that uses pulse module 2, enter a connector number
using a number in the range of between 1 and the maximum number
of axes for pulse module 2. When pulse module 2 need not be used,
enter 0. If a number that falls outside the valid range is entered, the
message FORMAT ERROR is displayed.
D 1–DSP
Enter 1, each of which exclusively uses a DSP, which is usually
shared by two axes. If a number other than 0 or 1 is entered, the
message ***F.54–8*** is displayed.
D CS
Not used.
D TNDM
Enter odd and even numbers for the master and slave axes for
tandem control. These numbers must be consecutive and in the
range of between 1 and 8. If a number that falls outside the valid
range is entered, the message FORMAT ERROR is displayed.
When the [SETING] soft key is pressed on the axis setting screen after
data entry, the message DATA IS OUT OF RANGE is displayed if any
of the following conditions is satisfied.
D Both M1 and M2 are nonzero for an axis.
D Any two of the 1–DSP, CS, and TNDM are nonzero for an axis.
D A duplicate value is specified for M1.
D A duplicate value is specified for M2.
D A duplicate value is specified for CS.
D A duplicate value is specified for TNDM.