4. SERVO FUNCTION DETAILS B-65150E/04
− 102 −
(3) Setting parameters
<1> To set a current control period of 125 µs, set the parameters as
follows:
#7 #6 #5 #4 #3 #2 #1 #0
1809
−
DLY1 DLY0 TIB1 DLY2 TRW1 TRW0 TIB0 TIA0
2004
−
Conventional
setting
00000110
Setting for level-up HRV control DLY1 DLY0 TIB1 DLY2 TRW1 TRW0 TIB0 TIA0
00000011
<2> Change the current loop gain (integral term).
1852
−
Current loop integral gain
2040
−
Set the standard parameter value multiplied by 0.8.
<3> Change the current loop gain (proportional term).
1853
−
Current loop proportional gain
2041
−
Set the standard parameter value multiplied by 1.6.
(4) Full utilization of level-up HRV control
Level-up HRV control allows the velocity gain to be increased by
decreasing the current control period. In addition, by optimizing each
element of the servo system, level-up HRV control can be fully utilized
to reduce machining figure errors. (See Subsec. 3.4.1.)
NOTE
Set the same current control period for two axes(*)
controlled by the same DSP.
For example, an axis for which No. 1023 = 1 is set,
and an axis for which No. 1023 = 2 is set are
controlled by the same DSP. So, the same current
control period must be set for these axes.
* An axis for which an odd number is set with the servo
axis number parameter (No. 1023), and an axis for
which the subsequent even number is set with the
same parameter are controlled as a set by the same
DSP.