B-65150E/04 4. SERVO FUNCTION DETAILS
− 289 −
<3> To specify measurement intervals, press the F5 key to display the
parameter setting screen.
Pressing numeric keys 1, 2, 5, and 0 can change the setting.
Usually select 1 ms.
Fig. 4.19 (g) Parameter setting screen
To return to the main screen after parameter setting, press the F10 key.
(9) Check pin board
Unlike conventional servo amplifiers, the servo amplifier module
(SVM) does not have a check pin. To observe signals in the servo
amplifier with an oscilloscope, connect the following check pin board
to the connector of the amplifier.
Ordering information Description
A06B-6071-K290 Printed-circuit board A20B-1005-0340
Cable (20 cm) A660-2042-T031#L200R0
(a) Printed-circuit board outline drawing
<1><2><3><4><5>
<20>
<6><7>
<11>
<9><10>
<18>
<12><13><14><15>
<16><17><19>
<8>
C
N
1
C
N
2
(b) Connectors to be used
SVM
J
X
5
C
N
1
C
2
Check pin board
N
Use numeric keys 1, 2, 5, and 0 to
specify a measurement interval.
The measurement interval should
usually be 1 ms.