B-63983EN/01 2.PMC SPECIFICATIONS
- 115 -
I/O Link input/output addresses
11910 I/O Link channel 1 input/output addresses
11911 I/O Link channel 2 input/output addresses
11912 I/O Link channel 3 input/output addresses
11913 I/O Link channel 4 input/output addresses
NOTE
Once any of these parameters is re-set, it is
necessary to turn the power off and on again.
[Input type] Parameter input
[Data type] Integer
[Valid data range] 0, 100 to 103, 200 to 203, 300 to 303, 900 to 903
This item specifies input/output addresses for an I/O Link channel.
Table 2.4.3 (c) I/O Link channel input/output addresses
Setting Input/output address
0 Standard setting (see below)
100 X0 to X127/Y0 to Y127 for the first PMC
101 X200 to X327/Y200 to Y327 for the first PMC
102 X400 to X527/Y400 to Y527 for the first PMC
103 X600 to X727/Y600 to Y727 for the first PMC
200 X0 to X127/Y0 to Y127 for the second PMC
201 X200 to X327/Y200 to Y327 for the second PMC
202 X400 to X527/Y400 to Y527 for the second PMC
203 X600 to X727/Y600 to Y727 for the second PMC
300 X0 to X127/Y0 to Y127 for the third PMC
301 X200 to X327/Y200 to Y327 for the third PMC
302 X400 to X527/Y400 to Y527 for the third PMC
303 X600 to X727/Y600 to Y727 for the third PMC
900 X0 to X127/Y0 to Y127 for the dual-check safety PMC