3.I/O LINK B-63983EN/02
- 170 -
Example of connection
DI module: +24 V common, 24 ms
(Example) AID32A1
DO module: 0 V common
(Example) AOD32A1
I/O unit
DI
module
DO
module
nother I/O unit
FS0 operator's panel
MAIN CPU
JD1A
(I/O Link)
PSU
CP6
24 VDC
I/O Link
JD1B
CP32
JD1A
M1A
M2A
CNC
Assignment method
For the group number ([GROUP]), set the group number used in the
configuration.
For the base number ([BASE]), always set 0.
For the slot number ([SLOT]), always set 1.
For the above example of connection, the FS0 operator's panel
occupies 32 points (4 bytes) for both input and output. Therefore, the
assignment names are as follows.
Input device assignment name Output device assignment name
ID32A OD32A
Operator's panel connection signals
Emergency stop signal (*ESP)
This signal is directly monitored by the CNC and is assigned at the
fixed address.
For connection, refer to the section describing the interface between
the CNC and PMC in the CNC connection manual.