B-65280EN/05 FANUC BUILT-IN SPINDLE MOTOR Bis series 2.EXPLANATION OF OPERATION MODES
- 581 -
15i 16i 30i
3122 4122 4122
Speed detection filter time constant
Unit of data : 0.1ms
Valid data range : 0 to 10000
Standard setting value : 0
This parameter sets a time constant for a filter to be applied to the
velocity feedback signal.
NOTE
Usually, this parameter need not be adjusted.
15i 16i 30i
3170 4170 4170
Overload current alarm detection level
Unit of data :
Valid data range : 0 to 32767
Standard setting value : Depends on the motor model.
NOTE
Usually, this parameter need not be adjusted.
15i 16i 30i
3345 4345 4345
Specified detection level of the spindle motor speed
Unit of data : 1 min
-1
Valid data range : 0 to 32767
Standard setting value : 0
This parameter sets the detection level of the spindle motor speed
detection function. If the specified spindle motor speed is greater than
the set value, the level of the speed specification detection signal
output from the spindle amplifier to the CNC becomes 1.
If the set value is 0, the level of the speed specification detection
signal is always 0.
15i 16i 30i
3346 4346 4346
Incomplete integral coefficient
Unit of data :
Valid data range : 0 to 32767
Standard setting value : 0
Set this parameter to use incomplete integral function for velocity loop
integral control.
NOTE
Usually, this parameter need not be adjusted.