7.COOLING
B–65162E/03
138
7
The use of an amplifier module listed below requires forced air cooling.
In this case, provide a fan motor.
When forced air cooling is provided, the power magnetics cabinet should
be designed so that cooling air from the fan motor does not leak out from
the cabinet.
Because of its operating environment, the fan motor may have to be
maintained or replaced. Therefore, special considerations should be
given to the installation and construction of the fan motor so that
maintenance work can be performed easily.
Table.7 AC Reactor
Model
Re-
quired
wind
speed
Usable fan
adaptor (Note)
Manufacturer part
number
PSM–11, SPM–11,
SPM–11HV
2 m/sec
or more
A06B–6078–K001
ROYAL ELECTRIC
UT857CG (R)
SVM1–130
(When motor α22/3000,
α30/3000, α40/2000 (with
fan), αL25/3000, αL50.2000,
or αM40/3000 is used)
SPMC–11
2 m/sec
or more
A06B–6078–K002
ROYAL ELECTRIC
UT857CG (R)
PSM–45,SPM–45,
PSM–75HV,SPM–75HV
2 m/sec
or more
A06B–6078–K003
ROYAL ELECTRIC
UTHC457C
STYLE ELEC-
TRONICS
US12D23
NOTE
Using a fan adaptor enables the desired cooling
performance to be obtained. For details of the fan adaptor,
see (7) in Section 2.2.3.