5. DIGITAL INPUT/OUTPUT MODULES CONNECTIONS B-61813E/03
−52−
(22) Output module AOA05E
Item Specifications
Points/module 5 points
Points/common 1 points/common
Rated load voltage 100 to 230VAC ±15%, 47 to 63Hz
Maximum load current 2A/point (howerver 5A/module)
Maximum rush current 25A ( 1 period)
Limit of load Refer to load derating curve (Fig. 5.3 (b))
Maximum voltage drop when ON 1.5Vrms
Maximum leak current when
OFF
3.0mA (115VAC), 6.0mA (230VAC)
OFF→ON
Max.1msResponse
time
ON→OFF
Half of the load
ferquency or
less
This is the value from input to output in the module. The actual value is
determined by adding it to the scanning time depending on each
system.
Output display LED display
External connection Terminal block connector (20 terminals, M3.5 screw terminal)
Fuse 3.2A, 1 piece for each output A0 to A4
Terminal connection and
circuitry