Power Mate
i
-MODEL D/H
Setting/punch operation for Ethernet Data
with DPL/MDI and DPL/MDI operation
package Specification
B-63354EN/04-01
EDIT DATE DESI
DESCRIPTION
9 /12
CUST.
SHEET
TITLE
DRAW.NO.
Data no
Data
0724 TCP port No.
(Data type): Double word
(Valid data range): 5001-65535
Specifies the port No. to be used by the DNC1/Ethernet function
within the range 5001 to 65565. This port No. must match with the
“NC TCP port No.” in the personal computer's Machine Setup
screen.
For details on how to set this, refer to the “FANUC FA SYSTEM for PC
OPERATOR'S MANUAL.”
Data no
Data
0725 UDP port No.
(Data type): Double word
(Valid data range): 5001-65535
Specifies the port No. to be used by the DNC1/Ethernet function
within the range 5001 to 65565.
This port No. must match with the “FANUC_C4_SERVER”in the
personal computer’s “services” file.
For details on how to set this, refer to the “FANUC FA SYSTEM for PC
OPERATOR'S MANUAL.”
Data no
Data
0726 Time interval .
(Data type): Double word
(Unit of data): 10 ms
(Valid data range): 0-65535
Specifies the interval at which broadcasting is carried out in 10 ms
units within the range 0 to 65535. If “0” to “9” is set as the interval,
broadcasting is not carried out. In other words, an interval less than
100 ms cannot be set.
Example)
When 100 is set, broadcasting is carried out at every 1 second
[1000 ms] (= 100 × 10).