Power Failure Backup Module
Descriptions
A-53866E-464
Operation to be performed at an instantaneous voltage drop
An instantaneous voltage drop of the amplifier instantaneous voltage drop guarantee time of 3
msec or less is not detected as a power failure, so that continuous operation is performed.
An instantaneous voltage drop of 7 msec or greater (detection delay time setting for path 1) is
detected as a power failure on path 1.
An instantaneous voltage drop of 3 msec to 7 msec may be detected as a power failure and may
not be detected as such so that continuous operation is performed, depending on the state of the
motor load: If, during an instantaneous voltage drop of 3 msec to 7 msec, the DC link voltage
drops to the power failure detection level for path 2, the drop is detected as a power failure and if
it does not drop to the power failure detection level for path 2, it is not detected as such so that
continuous operation is performed.
0 msec 3 msec 7 msec
Continuous operation
Power failure backup operationContinuous operation or power failure backup
operation (depending on the motor load at the
instantaneous voltage drop)
Instantaneous voltage drop time
Instantaneous voltage
drop guarantee time
Detection delay time
setting for path 1
Power failure detected
on path 1
Power failure detected
on path 2