Power Failure Backup Module
Descriptions
A-53866E-464
(18) Details of the connection of cable K93
This cable is used to supply 200 VAC for driving the dynamic brake module.
The α/αHV amplifier also supplies 200 VAC to the built-in AC fan of the SVM.
Cable type: Vinyl cabtyre cable, JIS C 3312, 2-conductor
Conductor: 1.25mm
2
(50/0.18), sheath: PVC 9.6
φ
Connector type: AMP connector
Receptacle housing: 1-178128-3
Receptacle contact: 1-175218-2
SVM/CX1A
200S
200R
(3)
(2)
(1)
200 VAC output UPS
S output
R output
Connections related to the supply of control power to amplifiers and the dynamic brake modules are
shown below.
[1] For the
αi/αHVi series amplifier
SVM
i
CX1A CX1B
CX8/CX9
CXA2B CXA2A
SPM
i
CXA2B CXA2A
SVM
i
CX1A CX1B
CX8/CX9
CXA2B CXA2A
PSM
i
CX1A CX1B
24V
CXA2A
DBM
Power failure
backup module
CX12
(CX27)
CX13
(CX28)
CX14
DBM
Uninterruptible power suppl
(UPS) 200V OUT AC200V
CNC, etc.
Normal operation: Supply 200 VAC.
Power failure: Supply DC voltage (300 VDC).
SPM
i
CXA2B CXA2A
K64
K4
K93
Control
power
supply
DC power supply
Built-in fan
K24
K25
K24
K25
K69
K69 K69
K69
K75
Built-in fan Built-in fan Built-in fan Built-in fan
Power supply
equipment
(24VDC output)
CAUTION
To an SVM using a dynamic brake module, be sure to supply 200 VAC from an
uninterruptible power supply (UPS) (by connecting cable K93).
If power is supplied to an SVM using a dynamic brake module from the power failure
ackup module (by connecting connector CX1A of the SVM to connector CX13 o
CX28 of the power failure backup module), the fuse in the power failure backup module
may be blown or the relay on the control board of the SVM may be damaged.