EDIT.
SHEET
DRAW. NO.
CUST.
TITLE
31
93
DESCRIPTIONDESIG.DATE
Power Failure Backup Module
Descriptions
A-53866E-464
(3) Details of the connection of cables K41 and K42
These cables are used to connect sub module R.
Cable type K41: Vinyl cabtyre cable, JIS C 3312, 2-conductor
Conductor: 2.0 mm
2
(37/0.26), sheath PVC 10.5φ
Cable type K42: Vinyl cabtyre cable, JIS C 3312, 2-conductore
Conductor: 0.75mm
2
(30/0.18), sheath PVC 8.8φ
Before connecting cable K42, remove the short bar between TH1 and TH2 of TB3.
The fan terminal of sub module R (A06B-6089-H712) needs not connection.
Sub module R (A06B-6077-H020 and A06B-6091-H020) has a cable that directly comes out from
the main body. Relay it using a terminal block or something similar, if needed.
If using two sub modules R (A06B-6089-H712), connect them as shown below.
Using two sub modules R (A06B-6089-H712)
NOTE
Use K78 between PSM (CX1B) and SPM (CX1A). (Do not use K4.)
Do not connect PSM (CX1B) and SVM (CX1A) together or SPM (CX1B) and SVM (CX1A) together.