Power Failure Backup Module
Descriptions
A-53866E-464
(7) Details of the connection of cable K61
The cable is used to transmit state and control signals between the power failure backup
module and the PMC. Back up the 24 VDC external power supply and the control power
supply for the PMC shown in the table below, using the power failure backup module,
so that the power can be maintained in the event of a power failure, in the same way
as the control power supply for the CNC.
Input signal rules (*SYNC)
Contact capacity 24 VDC+10% 10mA
Voltage drop across contacts
at closed circuit
2 V or less (including a cable voltage drop)
Output signal rules (RDY, *PFL, and *ALM)
ON-time maximum load current 200 mA or less including an instantaneous current
ON-time saturation voltage 1 V or less (at load current of 200 mA)
Withstand voltage 24 V+20% including instantaneous voltage
OFF-time leak current 20 µA or less
Delay time 50 µsec
Protection function If load current increases abnormally due to the
grounding of a cable or other reasons, the
protection function will operate and keep all
outputs OFF until the cause is removed.
Cable type: Vinyl cabtyre cable, JIS C 3307
Conductor: 1.25mm
2
(50/0.18)
Connector type: AMP connector
Receptacle housing: 1-178127-6
Receptacle contact: 1-175218-2