7.1.3 Power Failure Retract in a Machining Center and a Lathe
The general-purpose retract function option is required.
(For the FS0i-C, this is a standard function.)
As with the electronic gear box function, perform retraction with the retract signal (RTRCT).
When the power failure detection signal (*PFL) changes from "1" to "0", change the retract signal (RTRCT)
from "0" to "1".
*PFL
RTRCT
Power failure detected
*PFL: Power failure detection signal
Output from connector CX16 of the power failure backup module.
RTRCT: Retract signal
A rise from "0" to "1" is captured so that retraction is performed on the axis specified by a
parameter. The retract amount and the retract speed are those previously set with parameters.
Signal address Parameter number
CNC
RTRCT Retract speed Retract amount
FS16i/18i/21i/30i/31i/32i
FS0i-C
FS16-C/18-C
G066 #4 No.7740 No.7741
For details, refer to the connection manual (functions) and the parameter manual of the CNC