5.4 CHECKS
This section describes the checks required after CIMPLICITY viewer
setup.
If the CIMPLICITY viewer does not operate normally, review the
settings.
NOTE
The items checked in this section contain the
settings made in Sections 5.1 to 5.3.
Start checking after completion of all settings.
5.4.1 Checking Communication between the Viewer PC and Each
NC
When the CIMPLICITY viewer function is used with i CELL, the
viewer PC needs to communicate with NCs using the TCP/IP.
Check that the viewer PC can communicate with NCs using the
following procedure.
(1) Activate the FethDgn program on the viewer PC.
On the viewer PC, execute “Ethernet Diagnose” in program group
"CIMPLICITY i CELL."
(2) On the displayed screen, click the [Ping] tab and enter the IP
address of a destination NC in the [IpAddr] text field and click the
[Ping] button. When the settings are correct, "Reply" is displayed
as shown below:
Check that the IP address of the NC is displayed for "Reply."
If the above messages are not displayed, check the following
items:
• On the server PC, activate the FethDgn program and perform
the same check.
If the above messages are not displayed also on the server PC,
make the settings on the server PC and subsequent settings
again.
• When there is a router between the server and viewer PCs,
the router gateway setting is required for the viewer PC and
NCs.