B--63005EN/02
1. DISPLAY AND OPERATION
87
(1)Display start condition
100 : Draws a waveform for the stored data.
(2)Sampling period: Invalid
(3) Trigger: Invalid
(4)Data number: The table below lists the numbers of the data items for
which a waveform can be displayed (n = 1 to 8). Numbers for which
no data is stored cannot be specified.
Data No. Description Units
00 Does not display a waveform. --
0n Servo error (8 ms) for the n--th axis (positional devi-
ation)
Pulses
(detection units)
1n Pulse distribution for the n--th axis (move command) Pulses
(input increments)
2n Torque for the n--th axis (actual current) % (relative to maxi-
mum current)
5n Actual speed for the n--th axis min
-- 1
6n Command current for the n--th axis % (relative to maxi-
mum current)
7n Thermal simulation data for the n--th axis % (OVC alarm ratio)
(5)Data units: Weight of data when 1 is specified. The data units are
automatically specified for each data item and need not be set unless
the units must be changed for some reason.
[Valid data range] 1 to 1000
[Unit] 0.001
(6)Signal address: Invalid
D Waveform diagnosis
parameters (storage
type)