APPENDIXA. ALARM LIST
B--63005EN/02
708
Message Contents and solution
ER34 SLC ERROR(xx) The communication with the DI/DO units of the xx group failed.
(solution) Please confirm the connection of the cable connected to the DI/DO
units of the xx group.
Please confirm whether the DI/DO units turned on earlier than CNC and
PMC. Or, please exchange the module of PMC engine on the DI/DO
units of the xx group
ER35 TOO MUCH OUTPUT
DATA IN GROUP(xx)
The number of the output data in the xx group exceeded the max. The data, which
exceed 32 bytes, become ineffective.
(solution) Please refer to the following for the number of the data for each group.
“FANUC I/O Unit--MODEL A connecting and maintenance manual”
(B--61813E)
“FANUC I/O Unit--MODEL B connecting manual”(B--62163E)
ER36 TOO MUCH INPUT DATA
IN GROUP(xx)
The number of the input data in the xx group exceeded the max. The data, which
exceed 32 bytes, become ineffective.
(solution) Please refer to the following for the number of the data for each group.
“FANUC I/O Unit--MODEL A connecting and maintenance manual”
(B--61813E)
“FANUC I/O Unit--MODEL B connecting manual”(B--62163E)
ER38 MAX SETTING OUTPUT
DATA OVER(xx)
The assignment data for a group exceeds 128 bytes.
(The assignment data of output side of xx group or later become ineffective.)
(solution) Please reduce the assignment data to 128 bytes or less for the number
of
the output data of each group.
ER39 MAX SETTING INPUT
DATA OVER(xx)
The assignment data for a group exceeds 128 bytes.
(The assignment data of input side of xx group or later become infective.)
(Solution) Please reduce the assignment data to 128 bytes or less for the number
of
the input data of each goup.
ER98 ILLEGAL LASER CON-
NECTION
An I/O unit for the laser and assigned data do not match.
(solution) Check that the ladder assignment data and actual I/O units match.
ER99 X, Y96--127 ARE ALLO-
CATED
When the laser I/O link is provided, ladder I/O is assigned to X96--X127 and
Y96--Y127.
(solution) Delete the data assigned to X96 --X127 and Y96--Y127.
WN02 OPERAT E PANEL
ADDRESS ERROR
The address setting data of the operator ’s panel for FS --0 is illegal.
(solution) Please correct the address setting data.
WN03 ABORT N C--WINDOW/
EXIN
LADDER was stopped while CNC and PMC were communicating.
The functional instruction WINDR, WINDW, EXIN, DISPB, and etc. may not work nor-
mally.
(solution) When restarting the system, this alarm will be released. Execute the
sequence program(Press RUN key) after confirming whether there is a
problem in LADDER or not.
WN04 UNAVAIL EDIT MODULE The LADDER editing module cannot be recognized.(PMC--SAx/SBxx=1 to 3)
(solution) Please confirm the slot position installed.
Please confirm the installed module.
WN05 PMC TYPE NO CONVER-
SION
A ladder program for the PMC--SA3/SA5 was transferre d to the PMC--SB5.
(solution) Correct the ladder type.
WN06 TASK STOPPED BY DE-
BUG FUNC
Some user tasks are stopped by break point of the debugging function.
WN07 LADDER SP ERROR
(STACK)
When functional instruction CALL(SUB65) or CALLU(SUB66) was executed, the s tack
of the LADDER overflowed.
(solution) Please reduce the nesting of the subprogram to 8 or less.