3.LASER SEQUENCE CONTROL LASER FUNCTION B-64663EN/01
- 48 -
The timing chart for operations after the power is turned on is shown
below. In the figure, a solid line indicates the time during which a
signal is on or 1.
Oscillator stop sequence
To turn off the power to the laser oscillator, follow the procedure
below.
(1) When the discharge start signal (HVON) is set to 0 while the
oscillator is in the reference discharge state, the CNC stops
discharge, sets the oscillator signal (LSTR) to 0, and sets the
discharge start ready signal (LRDY) to 1.
(2) When the signal for starting oscillator (RUN) is set to 0 with the
LRDY signal set to 1, the CNC evacuates the fan system by
closing the laser gas supply valve and opening the exhaust valve.
At the same time, the CNC clears the LRDY signal to 0, and sets
the WAIT signal to 1.
(3) On completion of evacuation, the CNC starts purge processing.
For the Y series, since gas control is not performed, evacuation
and purge processing are omitted, and oscillator stop processing
is performed.
(4) When purge processing is completed, the CNC clears the chiller
start request signal CLON to 0, and sets purge completion signal
PURGE to 1.
When the PURGE signal is set 1, the power to the oscillator can
be turned off.