B–63503EN–1/01
4. REFERENCE POSITION ESTABLISHMENT
135
#7
1005
#6 #5 #4 #3 #2 #1 #0
ZRNx
[Data type] Bit axis
ZRNx When a command specifying the movement except for G28 is issued in
automatic operation (MEM, RMT, or MDI) when a return to the reference
position has not been performed since the power was turned on
0 : An alarm is generated. (P/S alarm 224).
1 : An alarm is not generated.
#7
1006
#6 #5
ZMIx
#4 #3 #2 #1 #0
NOTE
When this parameter is changed, turn off the power before
continuing operation.
[Data type] Bit axis
ZMIx The direction of reference position return
0 : Positive direction
1 : Negative direction
#7
1201
#6 #5 #4 #3 #2
ZCL
#1 #0
[Data type] Bit
ZCL Local coordinate system when the manual reference position return is
performed
0 : The local coordinate system is not canceled.
1 : The local coordinate system is canceled.
1240
Coordinate value of the 1st reference position on each axis in the machine
coordinate system
NOTE
After setting this parameter, turn the power off then on again
so that the setting will take effect.
[Data type] Two–word axis
[Unit of data]
Increment system IS–B IS–C Unit
Millimeter machine 0.001 0.0001 mm
Inch input 0.0001 0.00001 inch
Rotation axis 0.001 0.0001 deg