4. DESCRIPTION OF PARAMETERS
B–63010EN/02
114
#7
1902
#6
DCE
#5 #4 #3
STP
#2 #1
ASE
#0
FMD
NOTE
After this parameter has been set, the power must be turned
off then back on for the setting to become effective.
[Data type] Bit
FMD The FSSB setting mode is:
0 : Automatic setting mode.
(When information including an axis–amplifier relationship is set on
the FSSB setting screen, parameter Nos. 1023, 1905, 1910 through
1919, 1936, and 1937 are set automatically.)
1 : Manual setting 2 mode.
(Set parameter Nos. 1023, 1905, 1910 through 1919, 1936, and 1937
manually.)
ASE When automatic setting mode is selected for FSSB setting (when the FMD
parameter (bit 0 of parameter No.1902) is set to 0), automatic setting is:
0 : Not completed.
1 : Completed.
(This bit is automatically set to 1 upon the completion of automatic
setting.)
STP With the dual check safety function, in the self test mode at power–up, a
self test of safety output signal is:
0 : Performed. (At power–up, the “CARRY OUT A SAFETY TEST”
warning appears, and the self test execution request signal RQT is
output.)
1 : Not performed.
CAUTION
1 The STP bit is temporarily used if an MCC shut–off test of
safety output signal in the MCC shut–off test mode is not
wanted at power–up when the machine is adjusted, for
instance.
2 Even if STP is set to 1, an MCC shut–off test of safety output
signal in the MCC shut–off test mode is required when the
power is turned on after 24 hours have elapsed since the
completion of the previous MCC shut–off test.
WARNING
If STP is temporarily set to 1 for machine adjustment or the
like, reset STP to 0.
DCE The dual check safety function is:
0 : Disabled.
1 : Enabled.