4. DESCRIPTION OF PARAMETERS
B–63010EN/02
424
#7
8166
#6 #5 #4 #3 #2
OVL
#1
MIX
#0
SYN
NOTE
When this parameter has been set, the power must be
turned off before operation is contimued.
[Data type] Bit
SYN Three–path synchronous control is:
0 : Enabled.
1 : Disabled.
MIX Three–path composite control is:
0 : Enabled.
1 : Disabled.
OVL Three–path superimposed control is:
0 : Enabled.
1 : Disabled.
8180
Master axis with which an axis is synchronized under synchronous control
[Data type] Byte axis
[Valid data range] 1, 2, 3, ... to the maximum number of control axes, or 201, 202, 203, ...
to 200 plus the maximum number of control axes
This parameter specifies the number of the master axis with which an axis
is synchronized. When zero is specified, the axis does not become a slave
axis and is not synchronized with another axis. When an identical number
is specified in two or more axes, one master axis has two or more slave axes.
S Exercising synchronous control between two paths
In the parameter of a slave axis, specify the axis number of the master
axis with which the salve axis is to be synchronized.
Setting: 1 to 8
The value specified here must not exceed the maximum number of
control axes.
(Example 1) Synchronizing the Z
2
–axis with the Z
1
–axis
Path 1 Path 2
Parameter No.8180x 0 Parameter No.8180x 0
Parameter No.8180z 0 Parameter No.8180z 2
Parameter No.8180c 0
Parameter No.8180y 0
S Exercising synchronous control in a path
In the parameter of a slave axis , specify 200 plus the number of the
master axis with which the slave axis is to be synchronized.
Setting: 201 to 208
The value specified here must not exceed 200 plus the maximum
number of control axes.