B–63010EN/02
4. DESCRIPTION OF PARAMETERS
441
8316
Difference between reference counters for master and slave axes
(Synchronous control one pair)
NOTE
When this parameter is set, the power must be turned off
before operation is continued.
[Data type] 2–word
[Data unit] Detection unit
[Valid data range] –99999999 to 99999999
This parameter indicates the difference between the values in the
reference counter for the master axis and that for the slave axis.
NOTE
Once grid positioning has been completed, the difference
between the reference counters is automatically set in this
parameter. At this time, bit 1 (ATS) of parameter No.8302 is
set to 0.
8317
Torque difference alarm detection time (Synchronous control one pair)
[Data type] Word
[Data unit] ms
[Valid data range] 0 to 4000 (When 0 is set, 512 ms is assumed.)
This parameter specifies the period between the servo preparation
completion signal (SA <F000 bit 6>) being set to 1 and the check of the
torque difference alarm being started, for the torque difference alarm
detection function.
The set value is rounded up to the nearest a multiple of 16 ms.
When 100 is specified, 112 ms is assumed.[Example]