B-63950EN/02 4.DESCRIPTION OF PARAMETERS
- 99 -
[Input type] Parameter input
[Data type] Bit axis
# 7 ALGx The servo axis loop gain in the Cs contour control mode is:
0: Not matched with the Cs contour control loop gain.
1: Matched with the Cs contour control loop gain.
#7 #6 #5 #4 #3 #2 #1 #0
1815 RONx APCx APZx DCRx DCLx OPTx
[Input type] Parameter input
[Data type] Bit axis
NOTE
When this parameter is set, the power must be
turned off before operation is continued.
# 1 OPTx Position detector
0: A separate pulse coder is not used.
1: A separate pulse coder is used.
NOTE
Set this parameter to 1 when using a linear scale
with reference marks or a linear scale with an
absolute address zero point (full-closed system).
# 2 DCLx As a separate position detector, a linear scale with reference marks or
a linear scale with an absolute address zero point is:
0: Not used.
1: Used.
# 3 DCRx As a scale with absolute address reference marks:
0: A rotary encoder with absolute address reference marks is not
used.
1: A rotary encoder with absolute address reference marks is used.
NOTE
When using a rotary encoder with absolute address
reference marks, set also bit 2 (DCLx) of parameter
No. 1815 to 1.
# 4 APZx Machine position and position on absolute position detector when the
absolute position detector is used
0: Not corresponding
1: Corresponding
When an absolute position detector is used, after primary adjustment
is performed or after the absolute position detector is replaced, this
parameter must be set to 0, power must be turned off and on, then
manual reference position return must be performed. This completes
the positional correspondence between the machine position and the