4.DESCRIPTION OF PARAMETERS B-63950EN/02
- 38 -
4.8 PARAMETERS OF AXIS CONTROL/INCREMENT SYSTEM
#7 #6 #5 #4 #3 #2 #1 #0
1000 EEA
[Input type] Parameter input
[Data type] Bit
# 0 EEA An extended axis name and extended spindle name are:
0: Invalid
1: Valid
#7 #6 #5 #4 #3 #2 #1 #0
1001 INM
[Input type] Parameter input
[Data type] Bit path
NOTE
When this parameter is set, the power must be
turned off before operation is continued.
# 0 INM Least command increment on the linear axis
0: In mm (metric system machine)
1: In inches (inch system machine)
#7 #6 #5 #4 #3 #2 #1 #0
1002 IDG XIK AZR JAX
[Input type] Parameter input
[Data type] Bit path
# 0 JAX Number of axes controlled simultaneously in jog feed, manual rapid
traverse and manual reference position return
0: 1 axis
1: 3 axes
# 3 AZR When no reference position is set, the G28 command causes:
0: Reference position return using deceleration dogs (as during
manual reference position return) to be executed.
1: Alarm (PS0304) "G28 was specified when no reference position
is set" to be displayed.
NOTE
When reference position return without dogs is
specified, (when bit 1 (DLZ) of parameter No.1002 is
set to 1) the G28 command specified before a
reference position is set causes an alarm PS0304 to
be issued, regardless of the setting of AZR.