4.DESCRIPTION OF PARAMETERS B-63950EN/02
- 302 -
NOTE
The variables depend on the selected options.
Custom macro common variable addition option
Not selected Selected
Not
selected
#500 to #549 or
#100 to #149 and #500 to #549
#500 to #999 or
#100 to #199 and #500 to #999
Embedded
macro
option
Selected
#500 to #549 or
#100 to #499 and #500 to #549
#500 to #999 or
#100 to #49 and #500 to #999
# 4 CRO ISO code in BPRWT or DPRNT command
0: Outputs only “LF” after data is output
1: Outputs “LF” and “CR” after data is output
# 5 TCS Custom macro (subprogram)
0: Not called using a T code
1: Called using a T code
# 6 CCV Common variables #100 to #149(NOTE) cleared by power-off are:
0: Cleared to <null>
1: Not cleared
NOTE
The variables depend on the selected options.
Custom macro common variable addition option
Not selected Selected
Not
selected
#100to#149 #100to#199
Embedded
macro
option
Selected
#100to#499
#7 #6 #5 #4 #3 #2 #1 #0
6003 MUS MSB MPR TSE MIN MSK
[Input type] Parameter input
[Data type] Bit path
NOTE
When this parameter is set, the power must be
turned off before operation is continued.
# 1 MSK Absolute coordinates at that time during custom macro interrupt
0: Not set to the skip coordinates (system variables #5061 and later)
1: Set to the skip coordinates (system variables #5061 and later)
# 2 MIN Custom macro interrupt
0: Performed by interrupting an in-execution block (Custom macro
interrupt type I)
1: Performed after an in-execution block is completed (Custom
macro interrupt type II)