B–64113EN–1/01
4. REFERENCE POSITION ESTABLISHMENT
229
Number Message Description
090 REFERENCE RETURN
INCOMPLETE
1. The reference position return can-
not be performed normally because
the reference position return start
point is too close to the reference
position or the speed is too slow.
Separate the start point far enough
from the reference position, or
specify a sufficiently fast speed for
reference position return.
2. During reference position return
with the absolute–position detector,
if this alarm occurs even though
condition 1 is satisfied, do the fol-
lowing:
After turning the servo motor for the
axis at least one turn, turn the power
off and then on again. Then per-
form reference position return.
091 REFERENCE RETURN
INCOMPLETE
Manual reference position return can-
not be performed in the feed hold state.
Perform a manual reference position
return in the automatic operation stop
state or reset state.
224 RETURN TO
REFERENCE POINT
Not returned to reference position before
cycle start. (Only when parameter ZRNx
(No. 1005#0) =0).
Do reference position return.
NOTE
P/S alarm No. 090 is issued when G28 is specified and the
reference position has not yet be established.
Alarm and message
Note