2.PREPARATIONS FOR OPERATION B-63943EN-1/02
- 346 -
2.3.4 Stroke Limit External Setting
Overview
When a tool is changed, the tool tip is aligned with the end of the limit
area and signals are input. This operation sets the machine position
(machine coordinates) at that time as the limit position in stored stroke
check parameters. A setting signal is provided for each direction of
each axis.
Signal
Stroke limit external setting signal +LM1 to +LM8<Gn110>, -LM1 to -LM8<Gn112>
[Classification] Input signal
[Function] Changes the values of the parameters for stroke check 1 (Nos. 1320
and 1321).
[Operation] When these signals are set to 1, the control unit changes the values of
the parameters (Nos. 1320 and 1321) using the machine coordinates
when the signals are input as the stroke check values.
Signal address
#7 #6 #5 #4 #3 #2 #1 #0
Gn110 +LM8 +LM7 +LM6 +LM5 +LM4 +LM3 +LM2 +LM1
Gn112 -LM8 -LM7 -LM6 -LM5 -LM4 -LM3 -LM2 -LM1