B-63943EN-1/02 2.PREPARATIONS FOR OPERATION
- 385 -
2104 Threshold for unexpected disturbance torque detection alarm
[Input type] Parameter input
[Data type] Word axis
[Unit of data] Torque command unit
[Valid data range] 0 to 7282 (The maximum motor torque is 7282, regardless of the
motor type.)
This parameter specifies the threshold load torque at which an
Unexpected disturbance torque detection alarm is issued.
Monitor the load torque by setting parameter TDOUT (No.2015#5) to
1 then, for this parameter (No. 2104), set a value larger than the
maximum monitored torque. An output of 4.4 V is equivalent to 7282
in the units of this parameter.
2142 Threshold for unexpected disturbance torque detection alarm for rapid
traverse
[Input type] Parameter input
[Data type] Word axis
[Unit of data] Torque command unit
[Valid data range] 0 to 7282 (The maximum motor torque is 7282, regardless of the
motor type.)
This parameter specifies the threshold load torque at which an
Unexpected disturbance torque detection alarm is issued.
Monitor the load torque by setting parameter TDOUT (No.2015#5) to
1 then, for this parameter (No. 2104), set a value larger than the
maximum monitored torque. An output of 4.4 V is equivalent to 7282
in the units of this parameter.
This parameter is enabled when ABG0 (bit 3 of parameter No. 2200)
= 1.
#7 #6 #5 #4 #3 #2 #1 #0
2200 ABG0
[Input type] Parameter input
[Data type] Bit axis
# 3 ABG0 The unexpected disturbance torque detection function for cutting or
rapid traverse is:
0: Disabled.
1: Enabled.
When this function is disabled, the threshold value during cutting feed
is used (parameter No. 2104).