B-65270EN/05 2. SETTING αiS/αiF/βiS SERIES SERVO PARAMETERS
- 9 -
2.1.2 Parameter Initialization Flow
On the servo setting and servo adjustment screens, set the following:
NOTE
1 When a separate detector of A/B phase parallel type and a serial linear scale are
used, Ns indicates the number of feedback pulses per motor revolution, sent from
the separate detector.
When a serial rotary scale is used, the number of pulses is calculated using
following expression: 12500 × (gear reduction ratio between the motor and table)
See (8)-(b)-2 in Subsec. 2.1.3.
In emergency stop state, switch on NC.
Initialization bits
Motor No.
MR
CMR
Move direction
Reference counter
Velocity gain
00000000 See (2) and (8)-(b)-3 in Subsec. 2.1.3.
See (3) in Subsec. 2.1.3.
See (4) in Subsec. 2.1.3.
See (5) in Subsec. 2.1.3.
See (7) in Subsec. 2.1.3.
See (9) in Subsec. 2.1.3.
Set 150% if the machine inertia is unknown.
(Equivalent to load inertia ratio parameter)
Which s
stem is bein
used?
Set flexible feed gear.
Make settings for using separate detector.
No. 1807#3 = 1, 1815#1 = 1 (Series 15i)
No. 1815#1 = 1 (Series 30i, Series 16i and so on)
Set flexible feed gear.
Number of velocity pulses
8192
Number of position pulses
12500
Number of velocity pulses
8192
Number of position pulses
Ns
Note 1
← See (6) in Subsec. 2.1.3. →
Turn power off then on.
End of parameter setting
Semi-closed loop Closed loop