3. αiS/αiF/βiS SERIES PARAMETER ADJUSTMENT B-65270EN/05
- 60 -
3.2 ACTIONS FOR ALARMS
If a servo alarm occurs, detail alarm information is displayed on the
diagnosis screen (Figs. 3.1 (b) and (d)). Based on this information,
check the cause of the servo alarm and take appropriate action. For
alarms with no action number, refer to relevant manuals such as the
maintenance manual on the amplifier.
Table 3.2 Alarm bit names
#7 #6 #5 #4 #3 #2 #1 #0
Alarm 1 OVL LVA OVC HCA HVA DCA FBA OFA
Alarm 2 ALD EXP
Alarm 3 CSA BLA PHA RCA BZA CKA SPH
Alarm 4 DTE CRC STB PRM
Alarm 5 OFS MCC LDM PMS FAN DAL ABF
Alarm 6 SFA
Alarm 7 OHA LDA BLA PHA CMA BZA PMA SPH
Alarm 8 DTE CRC STB SPD
Alarm 9 FSD SVE IDW NCE IFE
NOTE
The blank fields do not contain any alarm code.
(1) Alarms related to the amplifier and motor
Alarm 1 Alarm 5 Alarm 2
OVL LVA OVC HCA HVA DCA FBA MCC FAN ALD EXP
Description Action
1 0 0 Overcurrent alarm (PSM)
1 0 1 Overcurrent alarm (SVM) 1
1 0 1 Overcurrent alarm (software) 1
1 Excessive voltage alarm
1
Excessive regenerative discharge
alarm
1 0 0
Alarm indicating insufficient power
voltage (PSM)
1 1 0 Insufficient DC link voltage (PSM)
1 0 1
Insufficient control power voltage
(SVM)
1 1 1 Insufficient DC link voltage (SVM)
1 0 0 Overheat (PSM) 2
1 1 0 Motor overheat 2
1 1 1 Motor overheat
(Note)
2
1 MCC fusing, precharge
1 0 0 Fan stopped (PSM)
1 0 1 Fan stopped (SVM)
1
OVC alarm 3