G.PARAMETERS FOR α AND OTHER SERIES APPENDIX B-65270EN/05
- 480 -
G.4 PARAMETERS FOR SERVO HRV2 CONTROL
By converting parameter settings as shown below, servo HRV1
control parameters can be changed to parameters for servo HRV2
control.
NOTE
This section explains the conversion method to be
applied when only servo HRV1 control parameters
are provided. For motors for which servo HRV2
control parameters are provided, use these servo
HRV2 control parameters.
<1> To set the current control period to 125 µs, set the following:
#7 #6 #5 #4 #3 #2 #1 #0
1809(FS15i)
DLY1 DLY0 TIB1 DLY2 TRW1 TRW0 TIB0 TIA0
2004(FS30i,16i)
Conventional
setting
0 X 0 0 0 1 1 0
When servo HRV2 control is used DLY1 DLY0 TIB1 DLY2 TRW1 TRW0 TIB0 TIA0
0 X 0 0 0 0 1 1
The standard setting at the bit marked by X (bit 6) must be left
unchanged.
<2> Changing the current loop gain (integral)
1852(FS15i)
Current integral gain
2040(FS30i,16i)
Set a value obtained by multiplying the standard parameter value by
0.8.
<3> Changing the current loop gain (proportional)
1853(FS15i)
Current proportional gain
2041(FS30i,16i)
Set a value obtained by multiplying the standard parameter value by
1.6.